CHARGE LIMITS CALCULATOR FOR A2L REFRIGERANTS
Charge limit calculations apply to refrigerating systems, stationary or mobile of any size, excluding AC for transport vehicles, and are valid for occupied spaces above the ground. Calculations are based on Standard EN 378:1-2016.
Calculations based on QLMV or QLAV can only be used for an occupied space which fulfills all the following conditions:
- Systems where the refrigerant is classified as A1 or A2L according to EN 378-1:2016 Annex E
- Systems where the refrigerant charge does not exceed 1,5 * m3 (m3 = 150 m³ * LFL)
- Systems where the rated cooling (heating) capacity of the indoor unit is not more than 25 % of the total cooling (heating) capacity of the outdoor unit systems and where pipes serving equipment in the occupied. Space in question are not oversized relative to the capacity of that equipment.
- System location is class II in accordance with EN 378-1:2016, 5.3
- Systems where the heat exchanger in the indoor unit and the control of the system are designed to prevent damage due to ice formation
- Systems where the refrigerant-containing parts of the indoor unit are protected against fan breakage or the fan is designed to prevent breakage
- Systems where only permanent joints are used in the occupied space in question except for site-made joints directly connecting the indoor unit to the piping
- Systems where the refrigerant-containing pipes in the occupied space in question are installed in such way that it is protected against accidental damage in accordance with EN 378-2:2016, 6.2.3.3.4 and EN 378-3:2016, 6.2
- Alternative provisions to ensure safety are provided in accordance with EN 378-1:2016 C.3.2.1 and C.3.2.2
- doors of the occupied space are not tight-fitting
- effect of flow down is mitigated in accordance with EN 378-1:2016 C.3.2.4
- for the occupied spaces exceeding 250 m², the charge limits calculation shall use 250 m² as the room floor area for determination of the room volume
DISCLAIMER
Although Honeywell believes that the information contained herein is accurate and reliable, it is presented without guarantee or responsibility of any kind and does not constitute any representation or warranty of Honeywell, either expressed or implied. WITHOUT LIMITING THE FOREGOING, HONEYWELL DISCLAIMS THE WARRANTY OF MERCHANTABILITY, FITNESS FOR USE AND NON-INFRINGEMENT. Information provided herein does not relieve the user from the responsibility of carrying out its own tests and experiments, and the user assumes all risks and liabilities (including, but not limited to, risks relating to results, patent infringement, regulatory compliance and health, safety and environment) related to the use of the materials and information contained herein.
Maximum File Size
Maximum Files Exceeded
Due to inactivity you will be logged out in 000 seconds.
Maximum File Size
Maximum Files Exceeded
Honeywell International Inc. is committed to ensuring compliance with global laws that regulate its export and import activities. In following company procedures, it has been determined that is identified on a denied/restricted parties list that is applicable to this transaction.
As a result, Honeywell is unable to continue with this request.
CONTACT US
We’re here if you need us. Complete the form to connect with our team on any inquiry, including outreach to our sales or customer experience teams, tips on and troubleshooting with your portal or ecommerce profile, and to sign up for marketing communications.
Solstice Advanced Materials Inc.
115 Tabor Rd.
Morris Plains, NJ 07950
Copyright © 2025 Solstice Advanced Materials Inc.